Bypass Mixing Circuit

Technical Data Sheet

Product NameBypass Mixing Circuit
Product Code20.01.003
Max. Fluid Temperature in Primary Circuit90°C (Except circulation pump)
Max. Working PressurePN 10
Adjustment Range of Thermostatic Head20-60°C
Thermometer Measuring Range0-70°C
Capacity Coefficient of the Thermostatic Head at its Maximum Setting (Kv)2,75 m³/hours
Pump Connection Range180 mm
Bypass Valve Adjustment Range0,1 – 0,6 bar
Area of UseHeating Systems
Technical Drawings
PART NAMEMATERIAL TYPEMATERIAL SERIES
Main body parts, Connections, fittings, bypass groupBrass Casting, Brass hot forgingOTS 60Pb2, CW617N
Return Line, Capillary transmission pipe, Thermostatic SensorNickel Plated CopperDHP, CW024A
Connection O-RingsEthyl propylene elastomerEPDM 70Sh
Bypass valve flywheel, Thermostatic head body, Protection CoverAcrylonitrile – Butadiene – StyreneABS
Documents

Technical Information Brochure

Download
Installation and Operating Instructions
  1. Before assembly, do not remove it from the package until the moment of assembly, to prevent foreign matter from entering the bypass compact mixing circuit, which may affect its operation.
  2. Take precautions against any damage that may occur during transportation and shipment.
  3. Clean any foreign matter in your installation before installation.
  4. During installation, the valves on the bypass compact mixing circuit must be in the closed position.
  5. Do not use excessive glue or any other unsuitable substance during installation.
  6. Do not paint the bypass compact mixing circuit or contact it with corrosive chemicals.
  7. Do not use any other tool to open or close the bypass compact mixing circuit and do not remove the handles/flywheels of the valves.
  8. In case of any damage or malfunction in the bypass compact mixing circuit, it must be replaced by the authorities.
  9. It is mandatory to comply with the installation and usage instructions. Otherwise, the product will be out of warranty.
  10. Do not forget to get the warranty certificate. This document is only valid together with the corresponding invoice.